热平衡阀技术的供热原理及实际应用

2010-04-22 11:06:30 阅读6 评论0 字号:

译文:
近几年,北京市某些小区水力失调、热力失调十分严重,小区近端用户阻力损失小,供水从近端短路回到热力站中,造成近端用户室温髙,远端用户室温低,由此发生的投诉率很高。今年,通州一些小区,就发生了此类问题,尽管设计中采用了压力平衡阀及流量平衡阀,但近端室温髙,远端室温低现象仍未解决。 热平衡阀能有效地解决以上的问题,在一些小区使用效果{jj0}。其工作原理是通过测试流经阀体的热水温度,利用感温材料热胀冷缩的特性,自动开启或关小阀门的开度,从而自动调整水流量,水温高时,通过阀门的流量就小,甚至关闭;水温低时,水流量就大,甚至阀门xx打开,这种变化是随着温度的变化而变化的。 将热平衡阀安装在供暖系统的回水管路上,根据回水温度自动调节水流量,避免高温水直接短路到回水管路上,保证供水管路中的热水能够到达远端,能够充分利用热能,节约能源。而且热平衡阀上的手柄可以随时调整和设定回水温度,利用手持式红外线测温仪测试回水管外壁的温度就可以得到回水温度数据,便于调整回水温度。 过去入户管道多采用单管串联式设计,自力式热平衡阀的应用受到限制,多用于解决楼宇之间热平衡问题,而且由于对热平衡阀的性能认识的不广泛,往往在采暖系统出现供热不均衡问题以后,作为补救措施来使用。因此,生产厂家只生产40mm以上大口径热平衡阀,多用于热电、制药、石油化工等行业。 现在采暖系统入户管道实行双管并联方式,在采暖系统设计中多在供水管路中设置各种平衡阀;如果在设计中,在回水管线上设置热平衡阀,通过控制回水的温度和流量,从而控制进水流量,替代压力(流量)平衡阀,就可起到事半功倍的效果。

“ Heat Balance Valve technology theory and practical application of heat ”是由提供的国际阀门新闻,译文仅供参考。另外,中国气动阀门网还提供相关产品搜索:、、、、等。


原文:
In recent years, some communities of Beijing hydraulic disorder, thermal disorder is very serious, community resistance to the loss of proximal users is small, the water supply from the proximal short circuit back to heating station, causing a temperature Gao proximal users, remote users with low temperature, from This high rate of occurrence of complaints. This year, some of Tongzhou district, on the occurrence of such problems, although the design uses a pressure balance valve and flow balancing valves, but at room temperature Gao proximal and distal lower temperature phenomena remain unresolved. Heat balancing valves can effectively solve the above problems, the use excellent results in some quarters. It works by testing the water flows through body temperature, using temperature materials, thermal expansion and contraction characteristics, automatically open or close a small valve opening, which automatically adjusts the water flow, water temperature is high, through the valve traffic on the small, or even shut down; water temperature is low, the water flow on the major, or even the valve fully open, this change varies with the temperature of. The heat balance valve installed in the heating system back to the way water, return water temperature is automatically adjusted according to water flow, to avoid a direct short circuit to the hot water pipes back to the road, to ensure the water supply pipe in hot water to reach the remote, to take full advantage energy, energy conservation. And heat balance valve on the handle can adjust and set the return water temperature, using hand-held infrared thermometer tests the temperature of the water return wall return water temperature data can be easy to adjust the return water temperature. Pipeline over the past more than a single tube-home series design, self-application of heat balance valve is limited, and more to solve the heat balance between the buildings, but also as the performance of the heat balance valve is not widely known, often in the heating system, heating does not occur After balance, as a remedial measure to use. Thus, manufacturers produce only heat balance valve of large diameter above 40mm are used for thermal power, pharmaceutical, oil and chemical industry. Now households heating system pipes, double pipes in parallel, in the heating system design and more in the water supply pipe of various balancing valve; if the design, set the hot water return line balancing valves, by controlling the temperature and return water flow to control water flow, an alternative pressure (flow) balance valve, can play a multiplier effect.


原文来源:
<#--{zx1}日志--> <#--推荐日志--> <#--引用记录--> <#--相关日志--> <#--推荐日志--> <#--推荐阅读--> <#--右边模块结构--> <#--评论模块结构--> <#--引用模块结构-->
郑重声明:资讯 【热平衡阀技术的供热原理及实际应用- 中国气动阀门网的日志- 网易博客】由 发布,版权归原作者及其所在单位,其原创性以及文中陈述文字和内容未经(企业库qiyeku.com)证实,请读者仅作参考,并请自行核实相关内容。若本文有侵犯到您的版权, 请你提供相关证明及申请并与我们联系(qiyeku # qq.com)或【在线投诉】,我们审核后将会尽快处理。
—— 相关资讯 ——